Property typeCare home
ChallengeApproximately 85 litres of water lost per hour, with multiple possible internal sources
SolutionWhole-building visual inspection, outlet checks and meter isolation testing
Survey date17 March 2026
ResultActive water-loss sources identified across toilets, loft tanks and taps

The Challenge

Sheffield Care Home reported unexplained water usage of approximately 85 litres per hour. The external meter stopped when the internal stop tap was isolated, confirming that the loss was occurring downstream within the domestic hot or cold-water systems.

With numerous rooms, sanitary outlets and storage tanks across an operational care home, the investigation needed to determine whether the consumption came from one concealed leak or several localised defects.

Key Challenges

  • Reported loss of approximately 85 litres per hour
  • Large number of rooms, toilets, taps and water outlets
  • Multiple simultaneous sources of uncontrolled water use
  • Loft storage tanks continuously refilling
  • Need to separate fixture defects from a concealed supply leak

The Solution

A structured building-wide investigation combined room-by-room visual inspection with outlet checks, storage-tank assessment and meter isolation testing.

Whole-building inspection: Every room and outlet was checked. Passing toilets, a dripping kitchen tap and taps left running or not fully closed were identified.

Meter isolation: The internal stop tap was isolated and meter movement stopped, confirming that the loss was downstream within the internal domestic supply.

Storage tank assessment: Four loft tanks were inspected. Fill valves were observed continuously refilling and the installations appeared aged and in poor condition.

Control checks: The new downstairs shower room was inspected with no leak or operational issue observed, helping rule it out as a source.

The Results

The survey confirmed that the high water usage was not attributable to one single defect. Several active and preventable sources were contributing to the reported consumption.

  • Multiple toilet cisterns were continuously passing water to overflow
  • Loft cold-water storage tank fill valves were continuously refilling
  • Dripping and incorrectly closed taps were adding to water consumption
  • Meter response confirmed the loss was downstream of the internal stop tap
  • A focused repair plan was issued for toilet and tank fill valves
  • Non-concussive taps were recommended to reduce future waste
Inside a toilet cistern showing the fill valve and staining
Loft storage tank with the float valve continuously refilling
External water meter in its ground chamber

Why SOS Leak Detection?

This project demonstrates the value of a systematic, evidence-led investigation when high water usage may be distributed across several fixtures rather than one obvious leak.

  • Whole-building coverage

    Every room and outlet was inspected.
  • Evidence-led isolation

    Meter behaviour located the loss downstream of the internal stop tap.
  • Multiple-source diagnosis

    Toilets, storage tanks and taps were identified as contributing at the same time.
  • Actionable recommendations

    Findings were converted into a focused plumbing repair schedule.
  • Reduced future waste

    Non-concussive taps were recommended alongside the fill valve repairs.
Close-up of a tank fill valve and float
Loft storage tank forming a key investigation area

Contact Your Leak Detection Specialists Today

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

To help us, please select the options that best describe your leak

Leak Options
Drop files here or
Accepted file types: jpg, jpeg, png, gif, webp, bmp, pdf, Max. file size: 15 MB, Max. files: 5.