Property type Commercial forecourt with hand and drive-through car wash facilities
Challenge High water bills with no obvious internal damage and no visible leak in customer-facing areas
Solution Structured visual inspection, zone isolation, thermal imaging, moisture readings, pressure testing and acoustic testing
Result Issue isolated to the drive-through car wash facility, with additional exposed plant room leaks identified

The Challenge

A commercial forecourt site reported unusually high water consumption. No visible water damage was identified during the initial visual inspection, and the total volume of water loss was unknown.

The site contained several potential sources, including the shop area, bathrooms, hand car wash plant room, drive-through car wash plant room, water storage tank and external meter. The investigation needed to separate genuine system demand from pipework leakage.

The key objective was to confirm whether the loss was coming from the incoming and internal supply, operational car wash equipment or accessible plant room pipework.

Key Challenges

  • High water bills with no obvious damage inside the shop area
  • Multiple water-using zones requiring staged isolation
  • External meter showing continual movement during initial checks
  • Need to rule out incoming and internal supply pipework before targeting equipment
  • Visible plant room leaks present alongside constant car wash system demand

The Solution

SOS Leak Detection used a staged, evidence-led diagnostic process to narrow the source of water loss before any wider disruption or unnecessary repair work was recommended.

Visual inspection: Shop, bathroom, exterior and plant room areas were visually checked. No visible damage or raised moisture was identified in customer-facing areas.

Meter isolation: The external meter continued moving until the drive-through water storage tank supply was temporarily isolated, when the meter became static.

Non-invasive checks: Thermal imaging and moisture readings did not identify significant anomalies within the shop area.

Pressure and acoustic testing: A 30-minute pressure test showed no pressure loss on incoming and internal pipework. Acoustic testing found no significant sound anomalies on concealed car wash pipework.

The Results

The investigation gave the site a clear technical basis for action: the high water usage was linked to the drive-through car wash system and visible plant room leaks, rather than to the incoming and internal supply pipework.

  • External meter movement confirmed ongoing water loss during initial checks
  • Meter became static when the drive-through water storage tank supply was isolated
  • Water storage tank was registering a constant demand, with water entering the car wash channels
  • 30-minute pressure test found no loss on incoming and internal supply pipework
  • Thermal and moisture checks did not indicate an escape of water in the shop area
  • Additional small leaks were documented on exposed pipework in both plant room areas
Drive-through car wash bay with water in the channels
External water meter inside its chamber

Why SOS Leak Detection?

This project demonstrates the value of a structured, evidence-led approach when water usage is high but visible damage is limited.

  • Structured isolation

    The source was narrowed across multiple water-using zones.
  • Non-destructive evidence

    Thermal and moisture checks reduced guesswork.
  • Meter behaviour

    Meter readings confirmed the operational zone responsible for continued demand.
  • Clear diagnosis

    Internal pipework was separated from car wash system issues.
  • Focused repair route

    Attention was directed to the drive-through facility and exposed plant room leaks.
Leaking MDPE connection in the plant room
Exposed plant room pipework and valves

Contact Your Leak Detection Specialists Today

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

To help us, please select the options that best describe your leak

Leak Options
Drop files here or
Accepted file types: jpg, jpeg, png, gif, webp, bmp, pdf, Max. file size: 15 MB, Max. files: 5.