| Site type | Residential property, concealed heating pipework |
|---|---|
| Sector | Residential / Insurance |
| Challenge | Boiler faults and a constantly refilling feed and expansion tank |
| Solution | Tracer gas, endoscope inspection and floor access |
| Result | Leak repaired and retested; heating left in working order, reinstatement work advised |
The Challenge
SOS was appointed to investigate boiler problems and a feed and expansion tank that was constantly refilling. The resident reported that the boiler had stopped working.
Damp and low-level wall damage were observed in the hallway, front office and bedroom. Thermal imaging showed no significant anomalies. With the boiler unable to run the heating, further testing was needed to locate the water loss.
Key Challenges
- Boiler fault prevented the heating from running
- Feed and expansion tank constantly refilling
- No significant thermal imaging anomalies
- Membrane affected where tracer gas emerged
- Initial access did not expose the leaking fitting
The Solution
SOS inspected the damp areas, boiler and feed and expansion tank, then drained the heating pipework for tracer gas testing.
Tracer gas located an area beneath the bedroom floor. Endoscope inspection and further access were needed to expose the leaking fitting.
Initial checks: The boiler would not run, and the feed and expansion tank was constantly refilling. Damp was observed, but thermal imaging showed no significant anomalies.
Tracer gas testing: The heating pipework was charged with tracer gas at 0.7 bar. Pressure fell over two hours, confirming leakage. A reading of 600 ppm was detected near the bedroom radiator.
Targeted floor access: A damp-proof membrane was affected where gas emerged. Initial access exposed wet pipework without a visible leak. Endoscope inspection and further access found the fitting at the third opening.
Repair and retest: The leaking fitting was repaired and retested, with no further escape of water observed. The heating was left in working order and the floor openings were made safe.
The Results
The concealed heating leak was located, repaired and retested, with no further escape of water observed. The heating was left in working order and the floor openings were made safe. A water damage survey and permanent reinstatement were recommended.
- Pressure loss confirmed leakage during the two-hour test
- Tracer gas detected at 600 ppm near the bedroom radiator
- Leaking fitting exposed at the third floor opening
- Fitting repaired, with no further escape observed on retest
- Heating left in working order
- Floor access made safe; permanent reinstatement required
Why SOS Leak Detection?
SOS used tracer gas and endoscope inspection to locate a concealed heating leak after thermal imaging showed no significant anomalies. Targeted floor access exposed the leaking fitting for repair. Retesting checked the repair, and the report set out the work still required.
-
Confirmed leakage
Constant tank refilling prompted testing, and pressure loss confirmed a leak on the heating pipework. -
Combined investigation
Tracer gas and endoscope inspection guided the search for the fitting beneath the bedroom floor. -
Targeted floor access
The leaking fitting was exposed at the third opening after the initial access showed wet pipework. -
Verified repair
The fitting was repaired during the visit and retesting showed no further escape of water. -
Drying and reinstatement
A water damage survey was recommended to assess drying, followed by permanent reinstatement.