Case Study: High Water Usage Investigation
- Find out how we helped a commercial forecourt site with hand and drive-through car wash facilities get to the bottom of unusually high water bills - using a structured, evidence-led investigation to pinpoint the true source of loss without unnecessary disruption.
The Challenge
A commercial forecourt site reported unusually high water consumption. No visible water damage was identified during the initial visual inspection, and the total volume of water loss was unknown.
The site contained several potential sources, including the shop area, bathrooms, hand car wash plant room, drive-through car wash plant room, water storage tank and external meter. The investigation needed to separate genuine system demand from pipework leakage.
The key objective was to confirm whether the loss was coming from the incoming/internal supply, operational car wash equipment or accessible plant room pipework.
Key Challenges:
- High water bills with no obvious damage inside the shop area
- Multiple water-using zones requiring staged isolation
- External meter showing continual movement during initial checks
- Need to rule out incoming/internal supply pipework before targeting equipment
- Visible plant room leaks present alongside constant car wash system demand
The Solution
SOS Leak Detection used a staged, evidence-led diagnostic process to narrow the source of water loss before any wider disruption or unnecessary repair work was recommended.
Visual inspection:
Shop, bathroom, exterior and plant room areas were visually checked. No visible damage or raised moisture was identified in customer-facing areas.
Meter isolation:
The external meter continued moving until the drive-through water storage tank supply was temporarily isolated, when the meter became static.
Non-invasive checks:
Thermal imaging and moisture readings did not identify significant anomalies within the shop area.
Pressure and acoustic testing:
A 30-minute pressure test showed no pressure loss on incoming/internal pipework. Acoustic testing found no significant sound anomalies on concealed car wash pipework.
The Results
The investigation gave the site a clear technical basis for action: the high water usage was linked to the drive-through car wash system and visible plant room leaks, rather than to the incoming/internal supply pipework.
- External meter movement confirmed ongoing water loss during initial checks
- Meter became static when the drive-through water storage tank supply was isolated
- Water storage tank was registering a constant demand, with water entering the car wash channels
- 30-minute pressure test found no loss on incoming/internal supply pipework
- Thermal and moisture checks did not indicate an escape of water in the shop area
- Additional small leaks were documented on exposed pipework in both plant room areas
Why SOS Leak Detection?
This project demonstrates the value of a structured, evidence-led approach when water usage is high but visible damage is limited:
- Structured isolation — narrowed the source across multiple water-using zones
- Non-destructive evidence — thermal and moisture checks reduced guesswork
- Meter behaviour — confirmed the operational zone responsible for continued demand
- Clear diagnosis — separated internal pipework from car wash system issues
- Focused repair route — directed attention to the drive-through facility and exposed plant room leaks
Facing unexplained water usage?
SOS Leak Detection supports evidence-led non-destructive investigation that identifies likely causes of unexplained demand and helps clients move from uncertainty to focused remedial action.
Contact SOS Leak Detection
0800 046 3492
sosleakdetection.com
enquiries@sosleakdetection.com
Explore our leak detection services
Contact Your Leak Detection Specialists Today